Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 02/11/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MISSING WALL PLATES ON SWITCHES AND RECEPTACLES 2. GROUNDING ELECTRODE CONDUCTOR CUT AND MISSING INSTALL NEW GROUNDING ELECTODE SYSTEM AND BOND GAS AND WATER PIPING. SYSTEM TO INCLUDE 2 NEW GROUND RODS MIN. 6' APART |