Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. METAL ELBOW TO BE GROUNDED - NEC 250.80 2. PVC NOT ACCEPTABLE AS SERVICE RACEWAY ABOVE GROUND - C.O.T 3. J-BOX UNDERSIZED - NEC 314.28A 4. NEED BUSHING #4 AND LARGER CONDUCTOR - NEC 352.46 5. REMOVE ALL PAINT UNDER LUG FOOT - NOT JUST SCRATCH NEC 250.12 6. SPLICE CONNECTOR FOR SERVICE CONDUCTORS TO BE IDENTIFIED "AL-CU" - NEC 110.3B, 110.14 7. RACEWAYS, L.B TO BE SECURED WITHIN 36" OF ENCLOSURES 8. RESUBMIT DESCRIPTION OF WORK SO IT IS CORRECT THIS IS NOT A SERVICE UPGRADE, IT IS A REPAIR TO SERVICE CONDUCTORS AND SERVICE RACEWAY 9. ARRANGE SERVICE CONDUCTORS IN PANEL SO THEY DO NOT PRESS UP AGAINS PANEL COVER - NEC 408.5, 110.12 |