Permit: T08EL00202

Parcel: 11105030F

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. METAL ELBOW TO BE GROUNDED - NEC 250.80
2. PVC NOT ACCEPTABLE AS SERVICE RACEWAY ABOVE GROUND - C.O.T
3. J-BOX UNDERSIZED - NEC 314.28A
4. NEED BUSHING #4 AND LARGER CONDUCTOR - NEC 352.46
5. REMOVE ALL PAINT UNDER LUG FOOT - NOT JUST SCRATCH
NEC 250.12
6. SPLICE CONNECTOR FOR SERVICE CONDUCTORS TO BE IDENTIFIED "AL-CU" - NEC 110.3B, 110.14
7. RACEWAYS, L.B TO BE SECURED WITHIN 36" OF ENCLOSURES
8. RESUBMIT DESCRIPTION OF WORK SO IT IS CORRECT
THIS IS NOT A SERVICE UPGRADE, IT IS A REPAIR TO SERVICE CONDUCTORS AND SERVICE RACEWAY
9. ARRANGE SERVICE CONDUCTORS IN PANEL SO THEY DO NOT PRESS UP AGAINS PANEL COVER - NEC 408.5, 110.12