Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. DERATE CONDUCTORS PER 310.15 2. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH 200.6 3. FINISH LABELING CIRCUITS AS PER 408.4 |
|
| 03/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH LOAD SIDE |