Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00184
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. MESSAGE TO BE LEFT IN ENGLISH 2. PLANS TO BE ON SITE FOR INSPECTION 3. INSTALL ADDRESS LABEL ON SERVICE 4. INSTALL SERVICE SECONDARY CONDUCTORS 5. FINISH GROUNDING AND BONDING 6. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO NEUTRAL OR VIA ACCEPTABLE MAIN BONDING JUMPER - NEC 250.24 7. BOND SERVICE RACEWAYS - NEC 250.92 8. BOND TERMINATE ENCLOSURE - NEC 250.92 9. ALL CONDUCTORS TO BE IDENTIFIED - NEC 310.11 10. TIGHTEN ALL CONNECTIONS - NEC 110.3B 11. SERVICE SECONDARY RACEWAY NOT COMPLETE |