Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08EL00172

Parcel: 111030110


Addresses:

3420 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/10/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/27/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #8 PREVIOUS INSPECTION
05/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEPARATE NEUTRALS AND GROUNDS IN SUB-PANELS
2. SEAL UNUSED OPENINGS IN PANELS
3. GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH
4. RE-GROUND PHONE & TV TO SERVICE
5. PROPERLY IDENTIFY PHASE CONDUCTORS
6. CAP OLD SERVICE RACEWAY
7. BOND AROUND REDUCE WASHERS
8. SEWAGE PUMP WIRING NOT INSPECTED UNDER THIS PERMIT NEED SEPARATE PERMIT