Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2008 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 04/15/2008 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* 1) STILL NEED TO IDENTIFY SERVICE DISCONNECTS-NEC 230.72 B 2) FEEDERS/FUSES NOT IN YET |
|
| 04/11/2008 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The service is not per code.| 210* CORRECTIONS NOT COMPLETED ALSO, CONNECT G.E.C PROPERLY TO ACORN |
|
| 04/10/2008 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND SERVICE MAST - NEC 250.92 2. BOND NEUTRALS TO SERVICE DISCONNECT ENCLOSURES NEC 250.244C 3. IDENTIFY "SERVICE DISCONNECTS" AS SUCH - NEC 230.72B 4. FUSES/FEEDERS NOT IN 5. TIGHTEN ALL CONNECTIONS - NEC 110 6. BONDING CONDUCTOR TO BE SIZED PROPERLY - NEC 250.102C 7. GROUND RODS TO BE MINIMUM 6' APART - NEC 250 8. GROUND ROD ACORNS TO BE USED FOR CONDUCTOR SIZE LISTED - NEC 110.3B |