Permit: T08EL00172

Parcel: 111030110


Addresses:

3420 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
12/10/2008 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
04/15/2008 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
1) STILL NEED TO IDENTIFY SERVICE DISCONNECTS-NEC 230.72 B
2) FEEDERS/FUSES NOT IN YET
04/11/2008 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
The service is not per code.| 210*
CORRECTIONS NOT COMPLETED
ALSO, CONNECT G.E.C PROPERLY TO ACORN
04/10/2008 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
The service is not per code.| 210*
1. BOND SERVICE MAST - NEC 250.92
2. BOND NEUTRALS TO SERVICE DISCONNECT ENCLOSURES
NEC 250.244C
3. IDENTIFY "SERVICE DISCONNECTS" AS SUCH - NEC 230.72B
4. FUSES/FEEDERS NOT IN
5. TIGHTEN ALL CONNECTIONS - NEC 110
6. BONDING CONDUCTOR TO BE SIZED PROPERLY -
NEC 250.102C
7. GROUND RODS TO BE MINIMUM 6' APART - NEC 250
8. GROUND ROD ACORNS TO BE USED FOR CONDUCTOR SIZE LISTED - NEC 110.3B