Permit: T08EL00171

Parcel: 99999999P


Addresses:

1090 W DREXEL RD

Inspection Status: Not Applicable

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
03/27/2008 ELECTRIC - UNDERGROUND Not Applicable
03/20/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
PLANS REVISED
03/14/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
GROUND RING WITH 6 GROUND RODS & CADWELDS SUBJECT TO PLAN REVISION

OK 1" PVC CONDUIT NOT INSTALLED

1. PLANS CALL FOR STRANDED CONDUCTOR - PLEASE REVISE PLANS.