Permit: T08EL00159

Parcel: 12416005A


Addresses:

1440 S EUCLID AV

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/30/2008 ELECTRIC - FINAL Not ready for Inspection RETURN INSPECTION, OWNER REQUESTED AFTER HOURS INSPECTION $150 FEE PAID CHECK #0009929
GROUNDING TO SERVICE #2 COMPLETE
CALLED IN TO TEP MAP ROOM 3:30 PM
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
OWNER REQUEST UNSCHEDULED AFTER HR. INSP.
$150.00 FEE -- PAID CK#0009927

1. OLD NEUTRAL BLOCK INSTALLED IN NEW SERVICE DISCONNECT IS RUSTY AND RAIN DAMAGED, REPLACE WITH NEW, BOND NEUTRAL WITH BOND SCREW.
2. TERMINATE ALL EQUIP. GROUNDS TO ENCLOSURE AND BOND BUSHINGS PER 250 NEC
3. INSTALL REJECTION PINS

- ALL SERVICE GROUNDING ELECTRODE CONDUCTORS CUT
- DO NOT ENERGIZE DUST COLLECTOR DISC. SW WITHOUT INSPECTORS APPROVAL.