Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | RETURN INSPECTION, OWNER REQUESTED AFTER HOURS INSPECTION $150 FEE PAID CHECK #0009929 GROUNDING TO SERVICE #2 COMPLETE CALLED IN TO TEP MAP ROOM 3:30 PM |
|
| 01/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OWNER REQUEST UNSCHEDULED AFTER HR. INSP. $150.00 FEE -- PAID CK#0009927 1. OLD NEUTRAL BLOCK INSTALLED IN NEW SERVICE DISCONNECT IS RUSTY AND RAIN DAMAGED, REPLACE WITH NEW, BOND NEUTRAL WITH BOND SCREW. 2. TERMINATE ALL EQUIP. GROUNDS TO ENCLOSURE AND BOND BUSHINGS PER 250 NEC 3. INSTALL REJECTION PINS - ALL SERVICE GROUNDING ELECTRODE CONDUCTORS CUT - DO NOT ENERGIZE DUST COLLECTOR DISC. SW WITHOUT INSPECTORS APPROVAL. |