Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT WITH MINNIE 2) OK GROUND RODS 3) OK GAS AND WATER BOND 4) RECALL AFTER SWING OVER COMPLETE |