Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) A NEW GROUNDING ELECTRODE SYSTEM IS NEEDED FOR UPGRADE 2) PHYSICAL PROTECT BOND CONDUCTORS 3) BOND GROUNDING ELECTRODE TO GROUNDED TERMINAL AT SERVICE |