Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00134
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROMERO @ 349-8237 - SUB-PANEL IN UNIT HAS 100 AMP. MAIN, POWER CORD RATED AT 50 AMPS, CIRCUIT BREAKER IN PEDESTAL RATED AT 70 AMPS. - REPLACE BREAKER TO MATCH POWER CORD OR HARD WIRE UNIT FOR 100 AMPS. WITH ALL LISTED AND MATCHING COMPONENTS - USE APPROVED STRAIN RELIEF CONNECTOR FOR POWER CORD TERMINATION |
|
| 01/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDUIT CONNECTION IN SUB-PANEL LOOSE - EXPOSED WIRING IN WALLS - LOOSE RECEPTACLE BOXES - POWER CORD CUT OFF UNDER MOBILE HOME - USE QUALIFIED ELECTRICIAN OR LICENSED CONTR. TO DO WORK. PROVIDE LADDER FOR ROOF INSP. A REINSPECTION FEE WILL BE ASSESSED NEXT INSPECTION OF NOT IN CODE COMPLIANCE. |