Permit: T08EL00134

Parcel: 14023165A


Addresses:

6206 S PARK AV #24


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00134

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ROMERO @ 349-8237

- SUB-PANEL IN UNIT HAS 100 AMP. MAIN, POWER CORD
RATED AT 50 AMPS, CIRCUIT BREAKER IN PEDESTAL RATED
AT 70 AMPS.
- REPLACE BREAKER TO MATCH POWER CORD OR HARD WIRE UNIT FOR 100 AMPS. WITH ALL LISTED AND MATCHING COMPONENTS
- USE APPROVED STRAIN RELIEF CONNECTOR FOR POWER CORD TERMINATION
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CONDUIT CONNECTION IN SUB-PANEL LOOSE
- EXPOSED WIRING IN WALLS
- LOOSE RECEPTACLE BOXES
- POWER CORD CUT OFF UNDER MOBILE HOME
- USE QUALIFIED ELECTRICIAN OR LICENSED CONTR. TO DO WORK. PROVIDE LADDER FOR ROOF INSP.

A REINSPECTION FEE WILL BE ASSESSED NEXT INSPECTION OF NOT IN CODE COMPLIANCE.