Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SEAL ENTRANCE ABOVE CURRENT CARRING PARTS 2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 3. IDENTIFY UNGROUNDED (HOT) CONDUCTOR ENTIRE LENGTH 4. GROUNDED RECEPTACLES ON UNGROUNDED CIRCUITS |
|
| 02/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PROTECTIVE BUSHING FOR WIRES LEAVING BACK OF OLD PANEL 2. SEAL OPENING WITH NON-COMBUSTIBLE MATERIAL 3. EQUIPMENT GROUNDING CONDUCTOR NOT SIZED PROPERLY FOR 60 AMP BREAKER - NEC 250.122 4. PROPERLY IDENTIFY GROUNDED CONDUCTOR TO SUB-PANEL NEC 200.6 5. IT APPEARS THAT OPEN CONDUCTORS ARE RUN TO SUB-PANEL NEED TO BE APPROVED WIRING METHOD PER NEC 6. GROUND TELEPHONE |