Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00128
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY GROUND JET BUTTON J-BOX 2) NEED PROPER CONNECTOR FOR PIPE COMING OUT OF GROUND 3) STRAP FLEX WITHIN 12" OF TERMINATIONS 4) TIGHTEN ALL CONNECTIONS 5) TO CONDUCTORS NOT ALLOWED UNDER SAME LUG (GROUNDS IN CONTACTOR FOR J-BOX) |