Permit: T08EL00121

Parcel: 119041830


Addresses:

3525 S CLARK AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/01/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX IN FURNACE ROOM CANNOT BE EXPOSED
2. CONDUIT & RECEPTACLE ON ROOF NEEDS TO BE RATED FOR OUTDOOR USE, SUPPORT BOX.
01/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPLACE OLD DISCONNECT ABOVE SERVICE PANEL WITH AN OUTDOOR RATED TYPE
2. OPEN SPLICES IN FURNACE CLOSET (LIGHT)
3. SMOKE DETECTORS TOO LOW. MOUNT BETWEEN 6-12"
BELOW CEILING, 3' AWAY FROM COOLER REGISTERS
4. INSTALL GFI PROTECTED RECEPTACLE IN KITCHEN COUNTER BY SINK. ALSO, REPAIR LOOSE BOX ON WALL
5. NEED ACCESS TO BACK OF HOUSE & LADDER FOR ROOF.