Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STILL NEED DETAILED PANEL SCHEDULE 2. CANNOT TERMINATE #4 & #6 GROUND UNDER ONE LUG 3. PERMIT FOR A/C UNIT TO BE RENEWED AND INSPECTIONS TO BE SCHEDULED & DONE 4. PLEASE HAVE ABOVE ITEMS CORRECTED BEFORE NEXT INSPECTION TO AVOID REFEE |
|
| 01/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
| 01/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUND RODS MIN. 6' APART 2. BOND GAS & WATER PIPING 3. VERIFY PERMIT FOR NEW A/C UNIT. PROVIDE COPY OF PERMIT NEXT INSPECTION 4. INSTALL LISTED MAST BRACING 5. PROVIDE DETAILED PANEL DIRECTORY 6. SEAL OPENING IN BACK OF PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE SEALANT 7. METER SEALED & SERVICE ENERGIZED PRIOR TO INSPECTION - CANNOT SEE INTO METER SECTION 8. IS DRYER GAS OR ELECTRIC? IF ELECTRIC SHOULDN'T IT BE FED WITH #10 ON 2 POLE 30 |