Permit: T08EL00116

Parcel: 123050430


Addresses:

2118 E EDISON ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CALL FOR FINAL AFTER TEP TIE IN
2) FEEDER BETWEEN UNITS WILL BE REMOVED
01/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TRIMMING THE OTHER STRANDS OF THE FEEDER CONDUCTORS NOT APPROVED METHOD TO TERMINATE, USE PROPER SIZED LUGS
2. VERIFY WATER PIPE BONDING
3. RISER BRACE MUST BE SUPPORTED TO BLD. TRUSS, NOT JUST PLYWOOD OVER TRUSS OR JOIST
4. MAINTAIN A 36" DEDICATED SPACE IN FRONT OF SERVICE EQUIP.
5. PROVIDE LADDER FOR ROOF INSPECTION
6. 2" CONDUIT FITTINGS LOOSE