Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TEP TIE IN 2) FEEDER BETWEEN UNITS WILL BE REMOVED |
|
| 01/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TRIMMING THE OTHER STRANDS OF THE FEEDER CONDUCTORS NOT APPROVED METHOD TO TERMINATE, USE PROPER SIZED LUGS 2. VERIFY WATER PIPE BONDING 3. RISER BRACE MUST BE SUPPORTED TO BLD. TRUSS, NOT JUST PLYWOOD OVER TRUSS OR JOIST 4. MAINTAIN A 36" DEDICATED SPACE IN FRONT OF SERVICE EQUIP. 5. PROVIDE LADDER FOR ROOF INSPECTION 6. 2" CONDUIT FITTINGS LOOSE |