Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T08EL00102
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 04/02/2008 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* OK GROUNDS OK DEVICES |
|
| 04/01/2008 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* NOTE: 314.20 & 408.4 WILL APPLY |
|
| 03/24/2008 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS 1. BOND SUB-PANEL ENCLOSURE 2. NEED GROUNDING ELECTRODE SYSTEM & TERMINATE TO GROUNDED TERMINAL |
|
| 03/13/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* BUILDING 1. PROTECT MC CABLE IN STUDS 2. USE APPROVED FITTING BETWEEN BOXES 3. SUPPORT VDV CABLING IN WALLS (LOW VOLTAGE) 725.6, 800.24 SERVICE: 1. ONLY ONE CONDUCTOR PER LUG 2. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING AND CLEAN SURFACE UNDER LUG 3. BOND SERVICE DISCONNECT 4. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 5. INSTALL REJECTION PINS 6. PROTECT CONDUCTORS 300.4 7. MOUNTING SCREWS NOT TO BE DRYWALL SCREWS 8. IDENTIFY GROUNDING EQUIPMENT CONDUCTOR 9. LABEL DISCONNECT 10. REMOVE BOND SCREW AT SUB-PANEL |
|
| 03/10/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OPEN ALL DRYWALL TO SEE M/C IN WALLS 2. SUPPORT M/C CABLES AS PER CODE 330.30 3. POSSIBLY PROTECT M/C CABLES AT STUDS - 330.17, 300.4 |
|
| 01/25/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |