Permit: T08EL00102

Parcel: 12704245A


Addresses:

5025 E 5TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T08EL00102

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
04/02/2008 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
OK GROUNDS
OK DEVICES
04/01/2008 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
NOTE: 314.20 & 408.4 WILL APPLY
03/24/2008 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
OK TO COVER WALLS

1. BOND SUB-PANEL ENCLOSURE
2. NEED GROUNDING ELECTRODE SYSTEM & TERMINATE TO GROUNDED TERMINAL
03/13/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
BUILDING
1. PROTECT MC CABLE IN STUDS
2. USE APPROVED FITTING BETWEEN BOXES
3. SUPPORT VDV CABLING IN WALLS
(LOW VOLTAGE) 725.6, 800.24

SERVICE:
1. ONLY ONE CONDUCTOR PER LUG
2. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING AND CLEAN SURFACE UNDER LUG
3. BOND SERVICE DISCONNECT
4. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL
5. INSTALL REJECTION PINS
6. PROTECT CONDUCTORS 300.4
7. MOUNTING SCREWS NOT TO BE DRYWALL SCREWS
8. IDENTIFY GROUNDING EQUIPMENT CONDUCTOR
9. LABEL DISCONNECT
10. REMOVE BOND SCREW AT SUB-PANEL
03/10/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OPEN ALL DRYWALL TO SEE M/C IN WALLS
2. SUPPORT M/C CABLES AS PER CODE 330.30
3. POSSIBLY PROTECT M/C CABLES AT STUDS - 330.17, 300.4
01/25/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*