Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/24/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CANNOT RUN LOAD CONDUCTORS BEHIND SHIELDED BUSS AREA AT TOP OF PANEL - USE PROPER FITTING TO TERMINATE CONDUIT A CONNECTOR INSTALLED FROM INSIDE OUT IS NOT APPROVED, USE CLOSE NIPPLE - PANEL DOOR NEEDS TO OPEN AT LEAST 90 DEGREES |