Permit: T08EL00101

Parcel: 14025022D


Addresses:

1401 E MILTON RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/24/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CANNOT RUN LOAD CONDUCTORS BEHIND SHIELDED BUSS AREA AT TOP OF PANEL
- USE PROPER FITTING TO TERMINATE CONDUIT
A CONNECTOR INSTALLED FROM INSIDE OUT IS NOT APPROVED, USE CLOSE NIPPLE
- PANEL DOOR NEEDS TO OPEN AT LEAST 90 DEGREES