Permit: T08EL00098

Parcel: 122170200

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/13/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE DISCONNECT FOR EACH UNIT CANNOT BE LESS THAN 60 AMPS - NEC 230.79
2. PROVIDE APPROVED PLANS SHOWING SERVICE LOAD CALCULATIONS. FEEDER SIZES TO UNITS. GROUNDING AND BONDING.