Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00095
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEM #7 FROM PREVIOUS INSPECTION NEED TO INSTALL GROUND RODS & NEED TO CORRECT MISSING GROUNDING ELECTRODE SYSTEM ON THE 2 OTHER SERVICES ON BUILDING 2. NEED TO PROVIDE LADDER FOR INSPECTION OF ROOF HAVE ELECTRICAL CONTRACTOR CHECK ELECTRIC ON ROOF AND FIX ANY VIOLATIONS. |
|
01/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL WALL PLATES ON RECEPTACLES & SWITCHES 2. INSTALL CONNECTORS ON WIRES ENTERING PANEL 3. SEAL OPEN KNOCKOUTS IN PANEL 4. NEUTRAL CONDUCTOR CANNOT TERMINATE ON GROUND BOX 5. INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL 6. INSTALL PANEL COVER 7. GROUNDING ELECTRODE CONDUCTOR HAS BEEN REMOVED NEED TO INSTALL NEW GROUNDING ELECTRODE SYSTEM AND BOND GAS AND WATER PIPING. GROUNDING ELECTRODE CUT AND MISSING ON ALL 3 SERVICES TO BUILDING 8. PLEASE PROVIDE LADDER FOR ROOF ACCESS |