Permit: T08EL00095

Parcel: 12806255A


Addresses:

5921 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00095

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/20/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEM #7 FROM PREVIOUS INSPECTION
NEED TO INSTALL GROUND RODS & NEED TO CORRECT MISSING GROUNDING ELECTRODE SYSTEM ON THE 2 OTHER SERVICES ON BUILDING
2. NEED TO PROVIDE LADDER FOR INSPECTION OF ROOF
HAVE ELECTRICAL CONTRACTOR CHECK ELECTRIC ON ROOF AND FIX ANY VIOLATIONS.
01/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL WALL PLATES ON RECEPTACLES & SWITCHES
2. INSTALL CONNECTORS ON WIRES ENTERING PANEL
3. SEAL OPEN KNOCKOUTS IN PANEL
4. NEUTRAL CONDUCTOR CANNOT TERMINATE ON GROUND BOX
5. INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL
6. INSTALL PANEL COVER
7. GROUNDING ELECTRODE CONDUCTOR HAS BEEN REMOVED
NEED TO INSTALL NEW GROUNDING ELECTRODE SYSTEM AND BOND GAS AND WATER PIPING. GROUNDING ELECTRODE CUT AND MISSING ON ALL 3 SERVICES TO BUILDING
8. PLEASE PROVIDE LADDER FOR ROOF ACCESS