Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEM #3 FROM INSPECTION ON 2/8 2) STRAP #4 TO BLDG SURFACE 3) NEED PANEL DIRECTORY |
|
| 02/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUNDING ELECTRODE CONDUCTOR FROM PANEL TO GROUND ROD 2. COMPLETELY DRIVE GROUND RODS 3. INSTALL CLAMPS ON GROUND RODS LISTED FOR DIRECT BURY 4. NEED DETAILED PANEL DIRECTORY 5. USE PROPER FITTING FOR CONNECTION OF LB TO PANEL 6. SEAL OPENING BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 7. SEPARATE GROUNDS AT TERMINATION NOT LISTED FOR 6 WIRES TO BE TERMINATED TOGETHER 8. REMOVE PAINT @ GROUND CLAMP CONNECTIONS ON PIPES |
|
| 01/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SMOKE DETECTORS NOT INSTALLED PROPERLY NEED TO BE MIN. 4" DOWN FROM CEILING TO MAX. OF 12" 2. HAVE WIRES HANGING OUT OF CEILING BACK ROOM, LIGHT FIXTURE HAS BEEN REMOVED 3. HAVE OPEN WALLS WITH RECEPTACLES HANGING OUT OF BOXES. WHY ARE WALLS OPEN? WHAT OTHER WORK IS TAKING PLACE? 4. NEW SERVICE PANEL INSTALLED SINCE LAST INSPECTION. NEED TO PULL PERMIT FOR SERVICE UPGRADE. 5. ADDED NEW LIGHTS AND CEILING FAN BOX TO STUDY NEED TO BE ADDED TO PERMIT. ADD ALL NEW WORK TO PERMIT. |