Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL SERVICE PANEL COVER 2. EXTERIOR DRYER RECEPTACLE TO HAVE WEATHERPROOF IN USE TYPE COVER 3. WASHER RECEPTACLE TO BE GFI PROTECTED AND HAVE WEATHERPROOF IN USE TYPE COVER 4. PROVIDE GFI PROTECTION FOR ALL 120V KITCHEN COUNTER, BATHROOM AND EXTERIOR RECEPTACLES 5. INSTALL CONNECTOR FOR DISPOSAL CORD 6. NEED SMOKE DETECTOR WEST BEDROOM 7. HALL SMOKE DETECTOR NOT WORKING/TOO CLOSE TO WALL 8. OPEN BULB NOT ALLOWED IN CLOTHES CLOSET 9. RECEPTACLES MIS-WIRED 12 GA WIRE NOT ALLOWED TO "STAB" INTO RECEPTACLES - READ BACK OF RECEPTACLE. |
|
| 01/15/2008 | ELECTRIC - FINAL | Cancelled | CANCELLED PER PROPERTY MANAGER MARTHA #664-8909 | |
| 01/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |