Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL CLAMP TO SECURE GROUND ELECTRODE CONDUCTOR TO SERVICE ENCLOSURE 2. CADWELD TO GROUND ROD LOOSE 3. SUPPORT GROUND WIRE TO WALL OF HOUSE 4. USE LISTED RISER SUPPORT 5. NEED APPROVED PLAN |