Permit: T08EL00047

Parcel: 134172200


Addresses:

619 S MARVIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/25/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND WIRES MUST BE COLOR CODED GREEN AT FACTORY, NOT TAPED
2) ROMEX BELOW 8' MUST BE PROTECTED
3) USE BONDING BUSHING WHERE REDUCING WASHERS USED ON CONDUIT
02/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECALL WHEN ALL WORK COMPLETE