Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK WALLS 2. RECALL WHEN COMPLETE |
|
| 01/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL 2. NAIL PLATE WIRES LESS THAN 1 1/4" TO BURIED HOLE 3. INSTALL PROTECTIVE BUSHING ON ROMEX ENTERING EMT |