Permit: T08EL00040

Parcel: 135020080

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T08EL00040

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
01/09/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED
2. BATHROOM RECEPTACLES TO BE GFI PROTECTED THIS INCLUDES RECEPTACLE IN LIGHT FIXTURE
3. CLOTHES CLOSET LIGHT FIXTURES TO BE 100% ENCLOSED
4. SMOKE DETECTORS NOT INSTALLED PROPERLY.
TO BE 4"-12" DOWN FROM CEILING, 3' FROM VENT
5. RECALL WHEN READY