Permit: T08EL00038

Parcel: 133270170


Addresses:

8021 E ROSEWOOD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/16/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS
2. FILL UNUSED OPENING IN BACK OF PANEL
WITH A NON-COMBUSTIBLE PRODUCT
3. TIGHTEN LOOSE FITTINGS
4. ONLY ONE CONDUCTOR PER BREAKER LUG TERMINATION
5. CIRCUIT LABELING TO BE AS PER 408.4 -
NO GENERAL LABELING
6. FINISH DRIVING GROUND RODS FLUSH
7. RISER HARDWARE TO BE 1/4" MINIMUM
8. SERVICE ENTRANCE CONDUCTOR TO BE 3' FROM WINDOW