Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS 2. FILL UNUSED OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 3. TIGHTEN LOOSE FITTINGS 4. ONLY ONE CONDUCTOR PER BREAKER LUG TERMINATION 5. CIRCUIT LABELING TO BE AS PER 408.4 - NO GENERAL LABELING 6. FINISH DRIVING GROUND RODS FLUSH 7. RISER HARDWARE TO BE 1/4" MINIMUM 8. SERVICE ENTRANCE CONDUCTOR TO BE 3' FROM WINDOW |