Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE BASEBOARD HEATER TO WALL 2. RECEPTACLES TO BE WIRED AS LISTED - DO NOT "STAB" 12 GA WIRE 3. TIGHTEN ALL CONNECTIONS |
|
| 01/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED UNIT # CORRECTLY IDENTIFIED @ SERVICE 2. INSTALL SMOKE DETECTORS IN BEDROOM AND LIVING ROOM PER MANUFACTURES INSTRUCTIONS MINIMUM 36" FROM VENTS 3. PROVIDE GFI PROTECTION FOR KITCHEN COUNTER AND BATHROOM RECEPTACLES 4. SECURE BASEBOARD HEATERS TO WALL AND REPLACE T-STAT KNOBS 5. REPLACE PAINTED OVER DEVICES |