Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS ITEMS FROM 1/8/08 INSP. NEW PERMIT FOR INTERIOR - ALL TRADES - CAN BE OBTAINED AT 201 N. STONE |
|
| 01/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ONLY ONE CONDUCTOR UNDER ACORN LUG 2. DRIVE GROUND RODS FLUSH 3. A PERMANENT METAL ADDRESS LABEL IS NEEDED 4. USE CORRECT SIZED SERVICE ENTRANCE CONDUCTOR 5. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 6. LABEL CIRCUIT DIRECTORY TO BE LEGIBLE - NO ABBREVIATIONS - NO GENERAL LABELING - 408.4 7. FILL UNUSED OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 8. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 9. PLEASE VERIFY PERMIT FOR NEW WORK TO INTERIOR 10. PLEASE PROVIDE ROOF ACCESS TO INSPECT MAST BRACE ANCHOR TO JOIST |