Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00018
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* MANAGER STATED SHELVING TO BE REWORKED AND PANELS NOT TO BE BLOCKED. |
|
| 02/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEM #1 & #2 FROM PREVIOUS INSPECTION SHELVES TO BE PERMANENTLY REMOVED 2. EQUIPMENT GROUNDING CONDUCTOR NOT SIZED PROPERLY @ PANEL. HAVE 30 AMP CIRCUITS - NEC 250.122 3. WARMING OVEN NOT TO BE USED UNTIL INSPECTIONS ARE APPROVED 4. HAVE ALL ITEMS CORRECTED BEFORE NEXT INSPECTION TO AVOID REFEE 5. RECALL WHEN READY |
|
| 01/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPER FOR 30 AMP RECEPTACLES TO BOX & RECEPTACLE TO BE MIN. #10 2. REMOVE SHELVES FROM IN FRONT OF PANELS. NEED TO HAVE PROPER WORKING CLEARANCES. COULD NOT OPEN PANELS 3. PLAN CALLS FOR RECEPTACLE FOR NEW REFRIGERATOR TO BE GFI |