Permit: T08EL00018

Parcel: 13419042D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/24/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
MANAGER STATED SHELVING TO BE REWORKED AND PANELS NOT TO BE BLOCKED.
02/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEM #1 & #2 FROM PREVIOUS INSPECTION SHELVES TO BE PERMANENTLY REMOVED
2. EQUIPMENT GROUNDING CONDUCTOR NOT SIZED
PROPERLY @ PANEL. HAVE 30 AMP CIRCUITS - NEC 250.122
3. WARMING OVEN NOT TO BE USED UNTIL INSPECTIONS ARE APPROVED
4. HAVE ALL ITEMS CORRECTED BEFORE NEXT INSPECTION TO AVOID REFEE
5. RECALL WHEN READY
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BONDING JUMPER FOR 30 AMP RECEPTACLES TO BOX & RECEPTACLE TO BE MIN. #10
2. REMOVE SHELVES FROM IN FRONT OF PANELS. NEED TO HAVE PROPER WORKING CLEARANCES. COULD NOT OPEN PANELS
3. PLAN CALLS FOR RECEPTACLE FOR NEW REFRIGERATOR
TO BE GFI