Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2008 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 02/28/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE MAST IS CROOKED GOING INTO HUB - 110 2. PROVIDE A LISTED MAST BRACE - NOT OLD EMT - 230 3. SECURE SERVICE TO STRUCTURE - PLASTIC ANCHORS NOT HOLDING - USE LEAD OR EQUIVALENT - 110.13 4. PANEL DIRECTORY TO BE CLEAR, CORRECT, LEGIBLE 408.4 5. BRANCH CKT CONDUCTORS TO BE PROPERLY DE-RATED FOR AMPACITY - 310.15 6. CORRECTLY IDENTIFY WHITE USED AS HOT 7. SERVICE TO HAVE MINIMUM 3' FRONT CLEARANCE NEED TO CUT BACK TREE - 110 8. WATER BOND CONDUCTOR UNDERSIZED -- 250.66 9. MAX. 15 AMP. BREAKER ON 14 GA. CONDUCTOR 10. AT J-BOX USE NEW 3R J-BOX - NOT OLD PANEL ENCLOSURE 11. BOND GAS PIPE? 12. CONDUCTOR TO BE BURIED/SECURED TO STRUCTURE 13. REMOVE BOND FROM WATER TO J-BOX 14. GROUND NOT TO BE USED AS NEUTRAL |