Permit: T08EL00015

Parcel: 11108006A


Addresses:

3626 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/25/2008 ELECTRIC - SERVICE UPGRADE Approved
02/28/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE MAST IS CROOKED GOING INTO HUB - 110
2. PROVIDE A LISTED MAST BRACE - NOT OLD EMT - 230
3. SECURE SERVICE TO STRUCTURE - PLASTIC ANCHORS NOT HOLDING - USE LEAD OR EQUIVALENT - 110.13
4. PANEL DIRECTORY TO BE CLEAR, CORRECT, LEGIBLE 408.4
5. BRANCH CKT CONDUCTORS TO BE PROPERLY DE-RATED FOR AMPACITY - 310.15
6. CORRECTLY IDENTIFY WHITE USED AS HOT
7. SERVICE TO HAVE MINIMUM 3' FRONT CLEARANCE NEED TO CUT BACK TREE - 110
8. WATER BOND CONDUCTOR UNDERSIZED -- 250.66
9. MAX. 15 AMP. BREAKER ON 14 GA. CONDUCTOR
10. AT J-BOX USE NEW 3R J-BOX - NOT OLD PANEL ENCLOSURE
11. BOND GAS PIPE?
12. CONDUCTOR TO BE BURIED/SECURED TO STRUCTURE
13. REMOVE BOND FROM WATER TO J-BOX
14. GROUND NOT TO BE USED AS NEUTRAL