Permit: T08EL00014

Parcel: 124080990


Addresses:

1448 E 7TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS NOT COMPLETED
REFEE IF NOT CORRECT NEXT TIME
01/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL SMOKE DETECTORS PER MANUFACTURER INSTRUCTIONS AND MIN. 36" FROM VENT
2) PROVIDE GFI PROTECTION FOR KITCHEN COUNTER, BATH AND EXTERIOR RECEPTACLES
01/09/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL INSPECTOR 349-5029
01/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PERMIT FOR ALL INTERIOR ELECTRICAL WORK AND NEW A/C
2. THIS PERMIT FOR 200 AMP UPGRADE BUT
HAVE OLD 125 AMP SERVICE
3. SERVICE TO BE UNSEALED FOR INSPECTION
4. PANEL DIRECTORY TO BE COMPLETE,
CORRECT AND LEGIBLE - NEC 408.4
5. SERVICE TO HAVE PROPER FRONT WORKING CLEARANCE EXTENDING TO GRADE - NEC 110.26
6. BOND WATER PIPE, NOT UNION -- NEC 110.3B
7. BURY GROUND BETTER OR SECURE TO STRUCTURE
8. BLANKS ON TOP OF SERVICE TO BE W.P TYPE
9. IDENTIFY SERICE NEUTRAL OUT OF WEATHERHEAD
10. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS INTO SERVICE -- NOT SPLIT BOLT

PARTIAL INSPECTION