Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETED REFEE IF NOT CORRECT NEXT TIME |
|
| 01/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL SMOKE DETECTORS PER MANUFACTURER INSTRUCTIONS AND MIN. 36" FROM VENT 2) PROVIDE GFI PROTECTION FOR KITCHEN COUNTER, BATH AND EXTERIOR RECEPTACLES |
|
| 01/09/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/08/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL INSPECTOR 349-5029 |
|
| 01/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PERMIT FOR ALL INTERIOR ELECTRICAL WORK AND NEW A/C 2. THIS PERMIT FOR 200 AMP UPGRADE BUT HAVE OLD 125 AMP SERVICE 3. SERVICE TO BE UNSEALED FOR INSPECTION 4. PANEL DIRECTORY TO BE COMPLETE, CORRECT AND LEGIBLE - NEC 408.4 5. SERVICE TO HAVE PROPER FRONT WORKING CLEARANCE EXTENDING TO GRADE - NEC 110.26 6. BOND WATER PIPE, NOT UNION -- NEC 110.3B 7. BURY GROUND BETTER OR SECURE TO STRUCTURE 8. BLANKS ON TOP OF SERVICE TO BE W.P TYPE 9. IDENTIFY SERICE NEUTRAL OUT OF WEATHERHEAD 10. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS INTO SERVICE -- NOT SPLIT BOLT PARTIAL INSPECTION |