Permit: T08EL00009

Parcel: 107120770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) DOOR UNLOCKED-FRONT UNIT EAST UNIT
01/24/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS 2:27 PM
2) RECALL
01/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SMOKE DETECTORS NOT INSTALLED PROPERLY. MOUNTED TO LOW ON WALL NEED TO BE MIN. 4" TO MAX. 12" DOWN
2. INSTALL MISSING PLATE ON RECEPTACLE IN KITCHEN
3. IS SINGLE RECEPTACLE OUTSIDE BACK DOOR GFI PROTECTED
4. NEED PANEL DIRECTORY
01/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED SMOKE DETECTORS EACH BEDROOM AND HALLWAY
ALL NEW
2. PROVIDE GFI PROTECTION FOR KITCHEN COUNTER, BATHROOM AND EXTERIOR 120V RECEPTACLES
3. HAVE OPEN WIRING IN WALL AT HOOD LOCATION
4. NEED W.P COVER FOR RECEPTACLE UNDER SERVICE
5. HAVE OPEN WIRING UNDER SINK
6. IDENTIFY PANEL DIRECTORY
7. SERVICE TO BE SECURED TO STRUCTURE