Permit: T08EL00002

Parcel: 117080270


Addresses:

817 S 3RD AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00002

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS NOT COMPLETED
ALSO,
1. MULTIWIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES
2. SERVICE DEAD FRONT COVER MISSING
3. DRYER NOT PROPERLY WIRED
4. REGROUND TELCO & CATV
02/01/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- ONLY ONE GROUND WIRE TO LARGE LUG
- FILL UNUSED OPENING IN BOTTOM OF PANEL
- LABELING FOR BREAKERS TO BE LEGIBLE
ALSO, NO ABBREVIATIONS