Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETED ALSO, 1. MULTIWIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES 2. SERVICE DEAD FRONT COVER MISSING 3. DRYER NOT PROPERLY WIRED 4. REGROUND TELCO & CATV |
|
| 02/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - ONLY ONE GROUND WIRE TO LARGE LUG - FILL UNUSED OPENING IN BOTTOM OF PANEL - LABELING FOR BREAKERS TO BE LEGIBLE ALSO, NO ABBREVIATIONS |