12/12/2008 INSP - INITIAL CODE ENFORCMENT Approved RESPONDED TO CALL OUT AT 10:00 AM
T.F.D. ON SITE

HEAT DAMAGE TO ONE ELECTRICAL RECEPTACLE WHICH SUPPLIES POWER TO A AC/ HEATER WINDOW MOUNT UNIT. TENANT DID SHUT OVER CURRENT PROTECTION DEVICE OFF. MY INSPECTION RESULTS AND ACTIONS WERE AS FOLLOWS.

1. DAMAGED CIRCUIT WAS IDENTIFIED AND OVER CURRENT PROTECTION DEVICE IS TO REMAIN IN OFF POSITION UNTIL A REPAIR PERMIT IS OBTAINED BY A LICENCED CONTRACTOR TO REPAIR WORK.

2. NOTICE OF VIOLATION WAS ISSUED TO OWNER GAYLE SWAN BECK. 60 DAY TO OBTAIN AND SECURE PERMITS FOR REPAIR.

3. PHOTOS WERE TAKEN.

4. DURING INSPECTION I DID IDENTIFY OTHER ELECTRICAL VIOLATIONS
A. ADDED CIRCUITS TO WINDOW MOUNT AC UNITS
B. GROUNDING ELECTRODE SYSTEM LACK GAS BOND
C. MIS MATCH BREAKERS
D. LACK OF PANEL SCHEDULE, UNREADABLE MARKINGS, THIS IS IMPORTANT DUE TO BUILDING HAS OTHER TENANTS OCCUPYING SPACE.

ELECTRICAL DAMAGE TO THE STRUCTURE WAS ISOLATED AND NEUTRALIZED. THE BUILDING IS SAFE TO OCCUPIED. OWNER WAS GIVEN INSTRUCTIONS ON PERMIT PROCESS AND THE REQUIREMENTS OF A LICENCE CONTRACTOR TO REPAIR WORK.