Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T08DV08992
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2008 | INSP - FOLLOW UP CODE ENFORCE | Approved | VISITED SITE, ISSUE CREATING NO HOT WATER HAS BEEN REPAIRED AT THIS TIME. HOT WATER PIPE IN SAME TRENCH AS CHILLER COLD WATER PIPE, COLD WATER PIPE LEAKED, COLD WATER SURROUNDING HOT WATER PIPE DROPPING HOT WATER TEMP TO LUKE WARM. ALL LEAKS REPAIRED, HOT WATER RESTORED. COMPLIANCE, CLOSE CASE |
|
| 10/03/2008 | INSP - FOLLOW UP CODE ENFORCE | Approved | MET WITH BRIAN REGIONAL ENGINEER, RON FROM THRON, TRON, ISSUE IS GOING THROUGH CHILLER WATER LINE BREAKS, 48 DEGREES TEMP(COLD) HOT WATER LINE IS IN SAME TRENCH. HOT WATER LINE IS 130 DEGREES, WHEN 48 DEGREE COLD WATER HITS THIS HOT WATER LINE, WATER TEMP DROPS TO APPROX. 90-95 DEGREES. THIS IS WHAT IS SUPPLIED TO NUIT, AS BREAKS HAPPEN, CONTRACTORS ARE CALLED AND REPAIRS UNDERWAY. BRIAN STATED SHOULD HAVE THIS BEHIND THEM WITHIN NEXT 2 WEEKS. MANAGER KIM WILL ME IN THE LOOP ON BREAKS AND REPAIRS. |