Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T08DV01777
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2008 | INSP - INITIAL CODE ENFORCMENT | Approved | ELECTRICAL MODIFICATIONS HAVE DONE WITH OUT PERMITS TO SERVICE EQUIPMENT CONSISTING OF 4 DISCONNECTS INSPECTOR IS LABELING DISCONNECTS FROM LEFT TO RIGHT, DUE TO NO LABELING TO ONSITE EQUIPMENT. RISER IS BENT ON ROOF MISSING WEATHER HEAD DISCONNECT # 1 EQUIPMENT HAS DETACHED FROM BACKER BOARD MISSING KNOCK OUT EQUIPMENT NOT LABELED DISCONNECT # 2 2 ADDED CIRCUITS 3 WIRES TO LEFT TERMINAL / 2 WIRES TO RIGHT TERMINAL EQUIPMENT NOT LABELED EXPOSED WIRING DISCONNECT # 3 3 ADDED CIRCUITS 3 WIRES TO LEFT TERMINAL / 2 WIRES TO RIGHT TERMINAL EQUIPMENT NOT LABELED DISCONNECT # 4 INTERNAL FUSE HOLDER IS BROKEN EQUIPMENT NOT LABELED |