| 03/06/2008 | INSP - INITIAL CODE ENFORCMENT | Approved | ELECTRICAL MODIFICATIONS HAVE DONE WITH OUT PERMITS TO SERVICE EQUIPMENT CONSISTING OF 4 DISCONNECTS INSPECTOR IS LABELING DISCONNECTS FROM LEFT TO RIGHT, DUE TO NO LABELING TO ONSITE EQUIPMENT. RISER IS BENT ON ROOF MISSING WEATHER HEAD DISCONNECT # 1 EQUIPMENT HAS DETACHED FROM BACKER BOARD MISSING KNOCK OUT EQUIPMENT NOT LABELED DISCONNECT # 2 2 ADDED CIRCUITS 3 WIRES TO LEFT TERMINAL / 2 WIRES TO RIGHT TERMINAL EQUIPMENT NOT LABELED EXPOSED WIRING DISCONNECT # 3 3 ADDED CIRCUITS 3 WIRES TO LEFT TERMINAL / 2 WIRES TO RIGHT TERMINAL EQUIPMENT NOT LABELED DISCONNECT # 4 INTERNAL FUSE HOLDER IS BROKEN EQUIPMENT NOT LABELED |