Permit: T08CM04022

Parcel: 12701003W

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM04022

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/26/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
01/22/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/08/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PLANS DO NOT SHOW SIZE OF AC UNITS
2. PROVIDE DUCT SMOKE DETECTORS AS NEEDED
3. OK TO INSULATE DUCTING
4. BE SURE CONDENSATE DRAINS ARE TERMINATED TO AN APPROVED LOCATION.
01/02/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE CONICAL TAPS EQUAL TO 125 PECENT FREE AREA PER DETAIL
2) PROVIDE ENOUGH STRAPS TO AVOID FLEX DUCT SAGGING, DUCT CANNOT REST ON GRID
3) RETURN AIR DUCT AT ENTRY NOT SEALED