Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/22/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/08/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PLANS DO NOT SHOW SIZE OF AC UNITS 2. PROVIDE DUCT SMOKE DETECTORS AS NEEDED 3. OK TO INSULATE DUCTING 4. BE SURE CONDENSATE DRAINS ARE TERMINATED TO AN APPROVED LOCATION. |
|
| 01/02/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE CONICAL TAPS EQUAL TO 125 PECENT FREE AREA PER DETAIL 2) PROVIDE ENOUGH STRAPS TO AVOID FLEX DUCT SAGGING, DUCT CANNOT REST ON GRID 3) RETURN AIR DUCT AT ENTRY NOT SEALED |