Permit: T08CM04022

Parcel: 12701003W

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM04022

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/22/2009 ELECTRIC - INTERMEDIATE Partial Approval NEED LIGHTING CIRCUIT IDENTIFIED FOR FINAL
01/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEED MC CABLE STRAPPED 1 1/4 AWAY FROM EDGE OF STUD
01/02/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLUE SMURF 1' ENT CANNOT BE PUT INSIDE OF METAL STUD CHANNEL OR MC AND ENT NEEDS STRAPPING EVERY 3'
2) MC NEEDS TO BE STRAPPED AWAY FROM EDGE OF METAL STUD 1 1/4 TO CENTER OF STUD AND NEED APPROVED METHOD OF STRAPPING 3 MC'S ON METAL STUD
3) 4/ 4 BOXES NEED LISTED BRACKETS FOR BRACING NOT PIECES OF STUDS