Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | NEED LIGHTING CIRCUIT IDENTIFIED FOR FINAL | |
| 01/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED MC CABLE STRAPPED 1 1/4 AWAY FROM EDGE OF STUD |
|
| 01/02/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLUE SMURF 1' ENT CANNOT BE PUT INSIDE OF METAL STUD CHANNEL OR MC AND ENT NEEDS STRAPPING EVERY 3' 2) MC NEEDS TO BE STRAPPED AWAY FROM EDGE OF METAL STUD 1 1/4 TO CENTER OF STUD AND NEED APPROVED METHOD OF STRAPPING 3 MC'S ON METAL STUD 3) 4/ 4 BOXES NEED LISTED BRACKETS FOR BRACING NOT PIECES OF STUDS |