Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM04020
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) FOR FINAL PAINT ALL EXPOSED PVC ON ROOF 2) PROVIDE A PROTECTIVE COATING ON ARMAFLEX ON ROOF 3) PROVIDE DISCONNECTS WITH FUSES 4) PROVIDE BACK DRAFT DAMPERS FOR DRYER VENTS |
|
08/02/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 4TH AND 3RD FLOOR CONDENSATE OK IN GUEST ROOMS 2) PROVIDE BACK DRAFT DAMPERS FOR RELIEF HOODS |
|
07/12/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCT ON ROOF-OK FOR 1ST LAYER OF FIRE WRAP |
|
06/22/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER DUCT ABOVE CEILINGS IN COMMON AREA 1ST FLOOR |
|
06/20/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ADDRESS LAY IN FIRE DAMPERS WITH ENGINEER |
|
06/16/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/01/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED FIRE DAMPERS IN SHAFTS-OK TO CLOSE |
|
05/24/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER OF FIRE WRAP OK 2) OK FOR 2ND LAYER AND INSTALL HOOD 3) CHECKED FIRE DAMPERS 4TH FLOOR AND PARTIAL 3RD FLOOR 4) OK INSTALL REMAINING DAMPERS 5) LINE SETS OK TO COVER |
|
05/03/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT, SEALED JOINTS 4TH FLOOR CABLE TV & STORAGE OK TO PROCEED | |
04/29/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/28/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/19/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OKAY TO PRS SHEET ROCK GATE HOUSE |
|
04/18/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/12/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/30/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE |