Permit: T08CM04020

Parcel: 12810076B


Addresses:

384 S WILLIAMS BL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T08CM04020

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) FOR FINAL PAINT ALL EXPOSED PVC ON ROOF
2) PROVIDE A PROTECTIVE COATING ON ARMAFLEX ON ROOF
3) PROVIDE DISCONNECTS WITH FUSES
4) PROVIDE BACK DRAFT DAMPERS FOR DRYER VENTS
08/02/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 4TH AND 3RD FLOOR CONDENSATE OK IN GUEST ROOMS
2) PROVIDE BACK DRAFT DAMPERS FOR RELIEF HOODS
07/12/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCT ON ROOF-OK FOR 1ST LAYER OF FIRE WRAP
06/22/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER DUCT ABOVE CEILINGS IN COMMON AREA 1ST FLOOR
06/20/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ADDRESS LAY IN FIRE DAMPERS WITH ENGINEER
06/16/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/01/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED FIRE DAMPERS IN SHAFTS-OK TO CLOSE
05/24/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 1ST LAYER OF FIRE WRAP OK
2) OK FOR 2ND LAYER AND INSTALL HOOD
3) CHECKED FIRE DAMPERS 4TH FLOOR AND PARTIAL 3RD FLOOR
4) OK INSTALL REMAINING DAMPERS
5) LINE SETS OK TO COVER
05/03/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* SUSPENDED ROUGH DUCT, SEALED JOINTS 4TH FLOOR CABLE TV & STORAGE OK TO PROCEED
04/29/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/28/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/19/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OKAY TO PRS SHEET ROCK GATE HOUSE
04/18/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/12/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/30/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO INSULATE