Permit: T08CM04020

Parcel: 12810076B


Addresses:

384 S WILLIAMS BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T08CM04020

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) FROM METER STUB TO ALL VALVES AT ALL LOCATIONS APPROVED TEST ONLY
06/30/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) TEST FOR INTERIOR (2) FIREPLACES OK
2) PROVIDE APPROVED 90 DEGREE AT GAS TO EXTERIOR BBQ AND INSTALL ALL REQUIRED VALVES
06/28/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) INSTALL PER APP. PLAN, PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS
06/06/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* 60 PSI TEST ON SYSTEM OK
WILL NEED 10PSI TEST ON ENTIRE SYSTEM AFTER APPLIANCE VALVE SHUTOFF INSTALLED
04/22/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
04/21/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
04/04/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
03/30/2011 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTERIOR P.E. REQUIRES CLEAN BEDDING AND MINIMUM 18" OF COVER WITH TEST GAUGE IN 1/10 POUND INCREMENTS