Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T08CM04020
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2011 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) FROM METER STUB TO ALL VALVES AT ALL LOCATIONS APPROVED TEST ONLY |
|
06/30/2011 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1) TEST FOR INTERIOR (2) FIREPLACES OK 2) PROVIDE APPROVED 90 DEGREE AT GAS TO EXTERIOR BBQ AND INSTALL ALL REQUIRED VALVES |
|
06/28/2011 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL PER APP. PLAN, PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS |
|
06/06/2011 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 60 PSI TEST ON SYSTEM OK WILL NEED 10PSI TEST ON ENTIRE SYSTEM AFTER APPLIANCE VALVE SHUTOFF INSTALLED |
|
04/22/2011 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* | |
04/21/2011 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
04/04/2011 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
03/30/2011 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTERIOR P.E. REQUIRES CLEAN BEDDING AND MINIMUM 18" OF COVER WITH TEST GAUGE IN 1/10 POUND INCREMENTS |