Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T08CM04019
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2009 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
05/13/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) SEPERATE GROUNDED AND GROUNDING CONDUCTORS AT 2ND DISCONNECT 2) PLANS FOR SERVICE DISCONNECT NOT AS INSTALLED. PLEASE REVISE PLANS 3) OK 2" PVC CONDUITS TO CELL EQUIPMENT 4) OK GROUND RING |