Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/08/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHITE COATED WIRE NOT ALLOWED AS LINE VOLTAGE WIRING - COAT WITH BLACK ELECTRICAL TAPE 2. UNIT #11 - RELOCATE UNIT TO ALLOW ACCESS TO WATER HEATER 3. COMPLETE ITEMS 1, 2, 5 ON LIST DATED 3/20/09 ALL ITEMS MUST BE COMPLETE PRIOR TO NEXT INSPECTION OR A REFEE WILL BE ASSESSED. |
|
| 03/23/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/20/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE MIN. R-8 INSULATION ON ALL DUCT EXPOSED TO EXTERIOR 2. FLEX DUCT MUST BE SUPPORTED MIN. OF 6" OFF GROUND 3. SEALTITE NOT APPROVED AS BURIAL CONDUIT 4. PROVIDE APPROVED DEPTH OF BURIAL TRENCH 5. PROVIDE PROPER P-TRAP AT UNITS 6. BREAKER NOT PROPERLY IDENTIFIED |