Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03995
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/27/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/07/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/19/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FUSES TO BE 30 AMPS FOR A/C UNIT |
|
12/07/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE: 1) NEED TO LABEL ALL EQUIPMENT 2) PLANS NOT REFLECTIVE OF WORK INSTALLED UNITS: 1) NM CABLE NOT FOR DAMP/WET LOCATION 2) NM NOT ALLOWED INSIDE OF UNITS 3) FILL UNUSED OPENINGS 4) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 5) CANNOT TAP CONDUCTORS AS DONE OFF OF 2 POLE 6) PHYSICALLY PROTECT LFNMC 7) USE CORRECT BREAKERS |
|
09/24/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |