Permit: T08CM03980

Parcel: 135084470


Addresses:

7230 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/22/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
06/19/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE GREASE RECEPTORS ON HOOD EXHAUST FANS
2) PROVIDE MIN. 6" BETWEEN HOOD AND EQUIPMENT
3) ALL ITEMS DATED 6/4/09 HAVE BEEN CORRECTED
06/04/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXTEND WATER HEATER VENT 3' ABOVE COOLER
I.D. ALL EQUIPMENT - NO INK
PROVIDE THE LISTED COVER OVER CONDENSOR ON ROOF
CONDENSORS ARE NOT PROPERLY FUSED
PROVIDE SUN SHIELDS OVER CANVAS CONNECTORS
PROVIDE ELEC. REQUIREMENTS FOR EXHAUST FANS ON ROOF
PROVIDE WING NUTS ON CLEANOUTS ON ROOF
NEED TO TEST HEAT SENSORS
AIR BALANCE OK
06/02/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*