Permit: T08CM03980

Parcel: 135084470


Addresses:

7230 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/01/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES IN KITCHEN
WILL CHECK WATER HEATER VENT ON FINAL
04/22/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/10/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/09/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1ST LAYER OF FIRE WRAP OK
OK FOR 2ND LAYER AND INSTALL DUCT
04/08/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/31/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
DISCUSSED TYPE I FAN INSTALLATION
03/27/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. REFERENCE DETAIL P2.1 (209) COND. CLEANOUT AT EACH CHANGE OF DIRECTION
2. REFERENCE DETAIL M3.0 (108) CONICAL TAP EQUAL TO 125% FREE AREA OR GREATER
3. SPACE ABOVE CEILING IS VENTED,
PROVIDE MIN. R-8 INSULATION ON ALL DUCT
03/25/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PLANS SHOW COPPER CONDENSATE PIPING RAN
INSIDE OF BLDG.
2. PROVIDE A LETTER FROM ENGINEER IF RUNNING ACROSS THE ROOF AND PROVIDE LETTER IF USING PVC INSTEAD OF COPPER.
3. OK TO SHEETROCK HARD LIDS
03/11/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*