Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES IN KITCHEN WILL CHECK WATER HEATER VENT ON FINAL |
|
| 04/22/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/10/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/09/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST LAYER OF FIRE WRAP OK OK FOR 2ND LAYER AND INSTALL DUCT |
|
| 04/08/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/31/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* DISCUSSED TYPE I FAN INSTALLATION |
|
| 03/27/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. REFERENCE DETAIL P2.1 (209) COND. CLEANOUT AT EACH CHANGE OF DIRECTION 2. REFERENCE DETAIL M3.0 (108) CONICAL TAP EQUAL TO 125% FREE AREA OR GREATER 3. SPACE ABOVE CEILING IS VENTED, PROVIDE MIN. R-8 INSULATION ON ALL DUCT |
|
| 03/25/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PLANS SHOW COPPER CONDENSATE PIPING RAN INSIDE OF BLDG. 2. PROVIDE A LETTER FROM ENGINEER IF RUNNING ACROSS THE ROOF AND PROVIDE LETTER IF USING PVC INSTEAD OF COPPER. 3. OK TO SHEETROCK HARD LIDS |
|
| 03/11/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |