Permit: T08CM03980

Parcel: 135084470


Addresses:

7230 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/19/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ITEMS 4, 7, 13, 14, 3
06/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RECEPTACLES WIRED INCORRECTLY
2. INSTALL BOX EXTENSIONS ON RECEPTS & SWITCHES
IN TILES
3. REMOVE PAINT FROM RECEPTACLES
4. USE ALL MOUNTING HARDWARE FOR RECEPTACLES IN INDUSTRIAL COVERS
5. MENU SIGN BOARD TO BE LISTED
6. MENU SIGN BOARD TO HAVE MANUFACTURES LABEL
7. SEAL RACEWAYS INTO WALK-IN's
8. FAN COIL UNITS IN WALK-IN's TO HAVE
DISCONNECTING MEANS
9. WIRE ICE MAKER, HW RECIRC PUMP
10. NEED PANEL DIRECTORIES
11. MISSING EM LIGHTS
12. ALL SIGNS TO BE LISTED & HAVE MANUFACTURES LABEL
13. CONDENSING UNIT OVERFUSED
14. INSTALL WEATHERPROOF ENCLOSURE MADE BY MANUFACTURER ON CONDENSING UNIT
15. FUSING FOR EXHAUST FANS NOT PER PLAN
16. BATHROOM EXHAUST FANS TO BE INTERLOCKED
WITH AC UNIT
17. HAVE ELECTRICAL CONTRACTOR INSTALL PER PLANS & NEC

RECALL WHEN READY