Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ITEMS 4, 7, 13, 14, 3 |
|
| 06/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLES WIRED INCORRECTLY 2. INSTALL BOX EXTENSIONS ON RECEPTS & SWITCHES IN TILES 3. REMOVE PAINT FROM RECEPTACLES 4. USE ALL MOUNTING HARDWARE FOR RECEPTACLES IN INDUSTRIAL COVERS 5. MENU SIGN BOARD TO BE LISTED 6. MENU SIGN BOARD TO HAVE MANUFACTURES LABEL 7. SEAL RACEWAYS INTO WALK-IN's 8. FAN COIL UNITS IN WALK-IN's TO HAVE DISCONNECTING MEANS 9. WIRE ICE MAKER, HW RECIRC PUMP 10. NEED PANEL DIRECTORIES 11. MISSING EM LIGHTS 12. ALL SIGNS TO BE LISTED & HAVE MANUFACTURES LABEL 13. CONDENSING UNIT OVERFUSED 14. INSTALL WEATHERPROOF ENCLOSURE MADE BY MANUFACTURER ON CONDENSING UNIT 15. FUSING FOR EXHAUST FANS NOT PER PLAN 16. BATHROOM EXHAUST FANS TO BE INTERLOCKED WITH AC UNIT 17. HAVE ELECTRICAL CONTRACTOR INSTALL PER PLANS & NEC RECALL WHEN READY |