Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RECEIVED LETTER TO ALLOW USE OF MC CABLE 2. REVISED PLANS TO GO THROUGH PLAN REVIEW NEED TO GET APPROVED 3. NEED TO INSTALL OCCUPANCY SENSORS PER PLAN. THESE CONTROL LIGHTS IN AREAS OF RESTRAINT 4. OK WALLS AND HARD LIDS |
|
| 03/13/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MC CABLE IS NOT APPROVED FOR USE SEE NOTE #3 ON SHEET E1. WHEN USING MC CABLE USE CONNECTORS LISTED FOR USE WITH MC CABLE 2. STRAP EMT WITHIN 3" OF CONNECTIONS 3. INSTALL MISSING MUD RINGS 4. CLOSE OPEN KNOCKOUTS IN EXISTING PANEL 5. CANNOT USE EMT FOR SUPPORT OF MC CABLE 6. PROPERLY STRAP PVC IN WALL 7. LIGHTS NOT PER PLAN OR FIXTURE SCHEDULE 8. BATHROOM EXHAUST FANS TO BE INTERLOCKED WITH AC2 9. OK PVC BUILDING SLAB 10. INSTALL PER PLANS AND NEC |