Permit: T08CM03978

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08CM03978

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
04/14/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE FACTORY TAPED CLEANOUT PLUGS WITH MACHINE SCREWS FOR ALL CLEANOUT COVERS
2) PROVIDE BACTERIA REPORT FOR POTABLE WATER SYSTEM WITH ACTUAL ADDRESS FOR THIS SUITE
3) WATER HEATER TEMPERATURE AND PRESSURE RELIEF SHALL TERMINATE PER APPROVED PLAN WITH 1" AIR GAP MINIMUM
4) PROVIDE ACCESS TO WATER HEATER FOR INSPECTION WITH MINIMUM ACCESS TO WATER HEATER FOR ABILITY TO SERVICE
5) SEE NOTE FOR LIMITING WATER TEMPERATURE AT PUBLIC USE LAV AT WATER HEATER DETAIL. NOTE: WATER HEATER HAS NOT BEE INSPECTED PLEASE SEE WATER HEATER DETAIL AND COMPLY WITH INSULATION REQUIREMENTS FOR 8' IN + 9' OUT AT WATER HEATER LOCATION OF INSULATION PER 2006 I.E.C.C.
6) PROVIDE ADA COMPLIANT FAUCET PER PLAN SPEC FOR LAV FAUCET
04/06/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. THIS INSPECTION FOR CLOSET FLANGE ONLY
2. COMPLETE PLUMBING AND PROVIDE BACTERIA REPORT FOR POTABLE WATER
3. CLOSET FLANGE OK

PLEASE CALL IN 03005, 03015, 03035, 03090