Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM03978
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
04/14/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE FACTORY TAPED CLEANOUT PLUGS WITH MACHINE SCREWS FOR ALL CLEANOUT COVERS 2) PROVIDE BACTERIA REPORT FOR POTABLE WATER SYSTEM WITH ACTUAL ADDRESS FOR THIS SUITE 3) WATER HEATER TEMPERATURE AND PRESSURE RELIEF SHALL TERMINATE PER APPROVED PLAN WITH 1" AIR GAP MINIMUM 4) PROVIDE ACCESS TO WATER HEATER FOR INSPECTION WITH MINIMUM ACCESS TO WATER HEATER FOR ABILITY TO SERVICE 5) SEE NOTE FOR LIMITING WATER TEMPERATURE AT PUBLIC USE LAV AT WATER HEATER DETAIL. NOTE: WATER HEATER HAS NOT BEE INSPECTED PLEASE SEE WATER HEATER DETAIL AND COMPLY WITH INSULATION REQUIREMENTS FOR 8' IN + 9' OUT AT WATER HEATER LOCATION OF INSULATION PER 2006 I.E.C.C. 6) PROVIDE ADA COMPLIANT FAUCET PER PLAN SPEC FOR LAV FAUCET |
|
04/06/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. THIS INSPECTION FOR CLOSET FLANGE ONLY 2. COMPLETE PLUMBING AND PROVIDE BACTERIA REPORT FOR POTABLE WATER 3. CLOSET FLANGE OK PLEASE CALL IN 03005, 03015, 03035, 03090 |