Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03970

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/24/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) CONFIRMED LEADING EDGES OF INSULATION SECURED INSIDE BLDG
2) STILL NEED TO SECURE LEADING EDGE OF SUPPLY DUCT INSULATION AT CONNECTION TO BOTTOM OF UNIT
3) CONFIRMED BATT INSULATION IN ROOF CURBS
4) OK FOR CEILING TILES
11/18/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ITEMS 2 & 3 DATED 10/7/09 STILL NOT VERIFIED, INSTALL CEILING TILES AT OWN RISK
2) PROVIDE MEANS OF ATTACHMENT BETWEEN CEILING REGISTERS, GRILLS AND STRUCTURE
10/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE CONDENSATE PIPING INSULATION PER SPECS
2) VERIFY BATT INSULATION IN CURBS PER PLANS/SPECS
3) PROVIDE METAL EDGE ON ALL EXPOSED INSULATION EDGES ON INTERIOR OF DUCT
4) PROVIDE CONDENSATE CLEANOUTS PER PLANS
5) OK TO ROCK HARD LIDS IN RESTROOMS MECH ONLY
09/25/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO CITY APPROVED PLANS ON SITE