Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM03970
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) CONFIRMED LEADING EDGES OF INSULATION SECURED INSIDE BLDG 2) STILL NEED TO SECURE LEADING EDGE OF SUPPLY DUCT INSULATION AT CONNECTION TO BOTTOM OF UNIT 3) CONFIRMED BATT INSULATION IN ROOF CURBS 4) OK FOR CEILING TILES |
|
11/18/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ITEMS 2 & 3 DATED 10/7/09 STILL NOT VERIFIED, INSTALL CEILING TILES AT OWN RISK 2) PROVIDE MEANS OF ATTACHMENT BETWEEN CEILING REGISTERS, GRILLS AND STRUCTURE |
|
10/07/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE CONDENSATE PIPING INSULATION PER SPECS 2) VERIFY BATT INSULATION IN CURBS PER PLANS/SPECS 3) PROVIDE METAL EDGE ON ALL EXPOSED INSULATION EDGES ON INTERIOR OF DUCT 4) PROVIDE CONDENSATE CLEANOUTS PER PLANS 5) OK TO ROCK HARD LIDS IN RESTROOMS MECH ONLY |
|
09/25/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CITY APPROVED PLANS ON SITE |